Showing posts with label architect. Show all posts
Showing posts with label architect. Show all posts

Monday, February 10, 2014

Changes to ASHRAE Ventilation Standard

Isaac Asimov wrote "Science gathers knowledge faster than society gathers wisdom." We have seen this play out countless times in residential construction: double pane windows with seals that failed within a few years creating 'obscurred glass', vapor barriers installed on the wrong side of the wall assembly causing rot to form, solar collectors on the roof that froze in winter, flexible polybutylene piping with only two fittings per line that still failed at the fitting, to name a few.  We are seeing it today in the form of airtight construction with little or no ventilation. Science has told us that building airtight homes will dramatically decrease heating and cooling costs, saving thousands over the life of a building. Compelling argument. The trouble is that many builders are not making the corollary adjustment: providing adequate planned ventilation.

The American Society of Heating, Refrigeration and Air Conditioning Engineers (ASHRAE) first published Standard 62.2:Ventilation and Acceptable Indoor Air Quality in Low-Rise Residential Buildings in 2003. The standard was published again in 2004 and every three years since then. It is a very readable and informative document that contains not only the recommendations of the Standard, but also a good description of ventilation and its importance in residential buildings. The Standard addresses (and describes) three primary requirements for ventilation. These are "whole-building", or dilution, ventilation; spot ventilation for removal of moisture and contaminants from specific rooms (bathroom, kitchen) or areas that tend to generate or contain problem quality air; and finally "source control". This last one is somewhat different than the prior two since it attempts to limit the sources of  air contaminants rather than remove them once in the air. The intent of ASHRAE is to have the standard adopted by building codes, not used as an educational tool. You may find it interesting to read their companion ASHRAE Guideline 24-2008 if you are looking for more explanation.

Both the 2004 and 2007 editions contained few changes, but the 2013 edition has a fairly significant change. The standard, acknowledging that homes are now being built universally tighter than in 2004, has eliminated an assumed air leakage rate of 2 cubic feet per minute (cfm) per 100 square feet of living space. To compensate for this loss of leakiness, the Standard increased the recommended ventilation rate from 7.5 cfm per person plus .01cfm per square foot to 7.5 cfm per person plus .03 cfm per square foot. The effect is to roughly double the recommended ventilation rate! For example, consider a family of four living in a 2500 square foot home. The old recommendation for ventilation was

 7.5 cfm/person * 4 people + .01 cfm * 2500 ft2 = 55 cfm.

The new recommendation is

 7.5 cfm/person * 4 people + .03 cfm * 2500 ft2 = 105 cfm.

This near doubling is seemingly in response to elimination of a 2 cfm leak assumption. In the example above, 2cfm of unintended ventilation were eliminated and 50 cfm were added. That's a big jump! This should be of particular note to people who are planning on using the standard to determine AMOUNT of ventilation and using negative pressure (exhaust only) as the METHOD of ventilation. It will be hard to meet the standard with exhaust only; you will likely be kept awake at night by the whistling of the make up air screaming through the small leaks in your building envelope. You will likely have such a large negative pressure that you may not be able to open your outward swinging doors; small birds may get sucked against the weather stripping of your windows as they try to fly by; you may raise the water table in your community..............I could go on with the hyperbole, but you probably get the point: you will have to maintain a large negative pressure to reach the recommended flow rate (CFM).

The new ventilation recommendations are a good argument for a balanced ventilation system, with a controlled inlet and outlet. A great way to achieve this is with a Heat Recovery Ventilator (HRV) or Energy Recovery Ventilator (ERV), formerly known as air to air heat exchangers. This type of system, coupled with kitchen and bath fans for spot ventilation, will easily be able to meet the standard and provide fresh air from a reliable location outside the house. 

ASHRAEs Standard 62.2 is not yet a part of the building code (the International Residential Code has not adopted it), so remains just a recommendation for now. However, inadequate ventilation results in poor indoor air quality (IAQ) where contaminants are allowed to reach unhealthy concentrations and relative humidity levels soar allowing mold to thrive. A thorough approach to ventilation examines the size and occupancy of the building to establish an acceptable flow rate as well as monitoring indoor air quality such as relative humidity and carbon monoxide to measure adequacy.
 

Friday, September 7, 2012

Searspark Gazebo


We recently traveled to East Hampton, Connecticut to raise the Governor William A. O'Neil Performing Arts Gazebo in Sears Park, located right on Lake Pocotopaug.  Mr. O'Neil, an East Hampton native,  was a popular governor of Connecticut from 1980-1989.

The gazebo bears his name in hand carved letters with flat black relief in crisp contrast to the western red cedar timbers.  In addition to the excellent natural rot resistance provided by the cedar, all the timbers are coated with our favorite oil-Land Ark Exterior.

The structure of the building is complex-what appears to be a simple hip roof from the exterior proves to be much more interesting as you enter the building and look up. The hip rafters are actually carried by two clear-spanning, flat topped trusses, similar to what you would see flanking a railroad bridge.  The two trusses run parallel to your entrance into the building, providing a clearly defined line of sight out to the lake. It is hard to decide whether to look out and admire the view or to look up and admire the view. The building tie-downs are stainless steel threaded rods concealed inside the 10x10 posts, attached to both the post and the concrete slab with acrylic based adhesive.  The roof sheathing is a nominal 3x6 end and edge grooved plank, made from three plies of Douglas fir laminated to together, capable of spanning twelve feet. This product eliminates the need for jack rafters, resulting in a clean roof structure, consisting of only principle and hip rafters.

The architect for this project was Cheryl Newton Architect LLC (www.cnarchitect.com) from Glastonbury, CT and the general contractor was Scope Construction (www.scopeconstruction.com) from New Britain, CT.

If you find yourself in East Hampton, stop in and take a look-the gazebo is hard to miss when you walk or drive in.  Park hours are 7AM-8PM.

If you are interested in having us design and build a gazebo for you, call or stop in at our shop-we are always happy to talk structure with you.Governor William A. O'Neill Performing Arts Gazebo Searspark in East Hampton, CT

Friday, May 25, 2012

Structural Insulated Panels Workshop for Architects


If you are not currently building or designing with Structural Insulated Panels, better known as SIPs, you have probably heard about them. We are offering a free informational workshop entitled, "Structural Insulated Panels-Building a Better Way" on Friday, June 1, 2010, at our campus from 12-1:00. (Brown bag lunch available for $12.) This presentation is an AIA approved program and qualifies for continuing education units. Please contact us for more information.